F3200 Installation & Programming Manual Document No: LT0122
System Specifications
Page 3-16 5 July 2001 Issue 2.7
MAF/PSU OUTPUTS (CONTINUED)
Option 1 Pole changeover contacts
Voltage-free
Snip Links Lk2, 3, 4.
Rating ELV only
30V, 2Adc resistive
30V, 1Adc inductive
24V, 1.5Adc inductive bells
Operation Programmable
Default Active on any unisolated zone alarm
Supervision On Bells +, - only
(ref 3.4.2)
Power Supply Outputs
0Vdc
Termination 1 non-demountable screw terminal
4sq mm max cable
2 demountable screw terminals
1.5sq mm max cable
1 2.8mm tab terminal (LED Display)
Battery Backed DC Supply
Rating 27.3Vdc nom.
(24V battery nom)
2Adc, fused.
+VBF1
Termination 1 non-demountable screw terminal
4sq mm max cable
1 demountable screw terminal
1.5sq mm max cable
+VBF2
Termination 1 non-demountable screw terminal
4sq mm max cable
1 demountable screw terminal
1.5sq mm max cable
1 2.8mm tab terminal (LED Display)